Thermal Overload Relays

Enquiry Us

Description

Differential thermal overload relays
for use with fuses or magnetic circuit-breakers GV2 L and GV3 L
■ Compensated relays with manual or automatic reset,
■ with relay trip indicator,
■ for a.c.
Relay setting
range (A)
Fuses to be used
with selected relay
Type
Rating
Reference
aM (A) gG (A)
Class 10 A (1) for connection by screw clamp terminals
0.10…0.16
0.16…0.25
0.25…0.40
0.40…0.63
0.63…1
1…1.6
1.6…2.5
2.5…4
4…6
5.5…8
7…10
9…13
12…18
16…24
23…32
30…38
17…25
23…32
30…40
37…50
48…65
55…70
63…80
80…104
LC10.25
0.5
1
1
2
2
4
6
8
12
12
16
20
25
40
40
25
40
40
63
63
80
80
80
2
2
2
2
4
4
6
10
16
20
20
25
35
50
63
80
50
63
100
100
100
125
125
160
E06…E38
E06…E38
E06…E38
E06…E38
E06…E38
E06…E38
E06…E38
E06…E38
E06…E38
E09…E38
E09…E38
E12…E38
E18…E38
E25…E38
E25…E38
E38
E40…E95
E40…E95
E40…E95
E50…E95
E65…E95
E80…E95
E80…E95
E95
LRE01
LRE02
LRE03
LRE04
LRE05
LRE06
LRE07
LRE08
LRE10
LRE12
LRE14
LRE16
LRE21
LRE22
LRE32
LRE35
LRE322
LRE353
LRE355
LRE357
LRE359
LRE361
LRE363
LRE365
Class 10 A (1) directly connected by connector
51…81
62…99
84…135
124…198
146…234
174…279
208…333
259…414
321…513
394…630
100
125
160
200
250
315
400
400
500
630
125
160
200
250
315
315
400
500
800
1000
E120…E160
E120…E160
E120…E160
E200
E200…E300
E250…E300
E250…E400
E300…E400
E500
E630
LRE480
LRE481
LRE482
LRE483
LRE484
LRE485
LRE486
LRE487
LRE488
LRE489

(1) Standard IEC 60947-4-1 specifies a tripping time for 7.2 times the setting current Ir:
Class 10A: between 2 and 10 seconds
(2) Direct mounting under contactor. For independent mounting of thermal overload relay
Order LAEB1 terminal block for LRE01…E35
Order LAEB3 terminal block for LRE322…E365