Description
DOL starters, non-reversing | ||||
This combination comprises of: ■ One 3-Pole EasyPact TVS contactor ■ One overload relay Short-circuit protection is provided by separate magnetic motor protection circuit breaker/fuse protection Please see EasyPact TVS catalogue for more information |
||||
Standard power rating of 3-phase motors 50/60Hz in AC3 400V |
Combination comprises of: Contactor Basic reference complete with code (1) |
Thermal overload relay Reference |
Setting range | |
kW | A | A | ||
0.06 | 0.2 | LC1E06•••• | LRE02 | 0.16 – 0.25 |
0.09 | 0.3 | LC1E06•••• LC1E06•••• |
LRE03 LRE04 |
0.25 – 0.40 0.40 – 0.63 |
0.12 0.18 0.37 0.55 |
0.44 0.6 1.1 1.5 |
LC1E06•••• LC1E06•••• LC1E06•••• LC1E06••• |
LRE05 LRE05 LRE06 LRE06 |
0.63 -1.0 0.63 -1.0 1.0 -1.6 1.0 -1.6 |
1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 |
2.7 3.6 4.9 6.5 8.5 11.5 15.5 18.1 22 29 35 41 55 |
LC1E06•••• LC1E06•••• LC1E06•••• LC1E09•••• LC1E09•••• LC1E12•••• LC1E18•••• LC1E25•••• LC1E25•••• LC1E32•••• LC1E40•• LC1E50•• LC1E65•• |
LRE08 LRE08 LRE10 LRE12 LRE14 LRE16 LRE21 LRE22 LRE22 LRE32 LRE355 LRE357 LRE359 |
2.5 – 4.0 2.5 – 4.0 4.0 – 6.0 5.5 – 8.0 7.0 – 10 9.0 – 13 12 – 18 16 – 24 16 – 24 23 – 32 30 – 40 37 – 50 48 – 65 |
37 | 66 | LC1E80•• LC1E80•• |
LRE361 LRE363 |
55 – 70 63 – 80 |
45 55 75 90 110 132 160 200 250 335 |
80 97 132 160 195 250 280 350 430 574 |
LC1E95•• LC1E120•• LC1E160•• LC1E200•• LC1E250•• LC1E250•• LC1E300•• LC1E400•• LC1E500•• LC1E630•• |
LRE365 LRE482 LRE483 LRE483 LRE484 LRE484 LRE486 LRE487 LRE488 LRE489 |
80 – 104 84 – 135 124 – 198 124 – 198 146 – 234 146 – 234 208 – 333 259…414 321…513 394…630 |
Accessories for reversing motor starter assembly | ||
Contactors with screw clamp terminals | ||
Using 2 identical contactors | Set of power connections |
Mechanical interlock |
Mechanical interlock | Reference | Reference |
LC1E06…E12 LC1E18/E25 LC1E32/E38 LC1E40…E65 LC1E80/E95 LC1E120/E160 LC1E200/E250 LC1E300…E500 LC1E630 |
LAEP1 LAEP12 LAEP2 LAEP3 LAEP4 DIY(1) DIY(1) DIY(1) DIY(1) |
LAEM1 LAEM1 LAEM1 LAEM1 LAEM4 LAEM5 LAEM6 LAEM7 LAEM8 |
Instantaneous auxiliary contact blocks for connection by screw lamps terminals |
||
– For use in normal operating environment | ||
Clip-on mounting | Number of contacts per block |
Reference |
Front | 1 NO / 1 NC 2 NO 2 NC 2 NO / 2 NC |
LAEN11 LAEN20 LAEN02 LAEN22 |
Time delay auxiliary contact blocks for connection by screw clamp terminals 8 A – 690 V |
||||
– For use in normal operating environment | ||||
Clip-on mounting (2) |
Number of contacts per block |
Time delay Type |
Setting range |
Reference |
Front | 1 NO / 1 NC | On-delay | 1…30 s | LAETSD |
Auxiliary contact blocks, add-on modules and accessories. | ||||||||
(1) Standard control circuit voltages. For other voltages please refer to catalogue. | ||||||||
a.c. supply | ||||||||
Volts | 24 | 48 | 110 | 220 | 240 | 380 | 415 | 440 |
LC1E06…300 | ||||||||
50Hz 60Hz |
B5 B6 |
E5 – |
F5 F6 |
M5 M6 |
U5 – |
Q5 Q6 |
N5 – |
R5 R6 |
LC1E400…630 | ||||||||
50/60 Hz | – | E7 | F7 | M7 | U7 | Q7 | N7 | R7 |
2) LC1E06 to E65: clip-on mounting on 35 mm 5 rail AM1 DP or screw fixing. LC1E80 to E95: clip-on mounting on 35 mm rail AM1DP or 75 mm rail AM1 DL or screw fixing. LC1E120 and E160: clip-on mounting on 2 x 35 mm 5 rail AM1 DP or screw fixing. |