Description
Standard power rating of 3-phase motors in category AC3 400/415V |
Circuit-breaker Setting ‘(1) range of thermal trips |
Contactor (1)(2)(3) |
|||
P kW |
le A |
lq kA |
A | Reference | Reference |
0.06 | 0.2 | 130 | 0.16…0.25 | GV2ME02 or GV2P02 |
LC1D09●● LC1D09●● |
0.09 | 0.3 | 130 | 0.25…0.40 | GV2ME03 or GV2P03 |
LC1D09●● LC1D09●● |
0.12 0.18 |
0.44 0.6 |
130 130 |
0.40…0.63 | GV2ME04 or GV2P04 |
LC1D09●● LC1D09●● |
0.25 0.37 |
0.85 1.1 |
130 130 |
0.63… 1 | GV2ME05 or GV2P05 |
LC1D09●● LC1D09●● |
0.55 | 1.5 | 130 | 1… 1.6 | GV2ME06 or GV2P06 |
LC1D09●● LC1D09●● |
0.75 | 1.9 | 130 | 1.6… 2.5 | GV2ME07 or GV2P07 |
LC1D09●● LC1D09●● |
1.1 1.5 |
2.7 3.6 |
130 130 |
2.5…4 | GV2ME08 or GV2P08 |
LC1D09●● LC1D09●● |
2.2 | 4.9 | 130 | 4… 6.3 | GV2ME10 or GV2P10 |
LC1D09●● LC1D09●● |
3 | 6.5 | 130 | 6… 10 | GV2ME14 or GV2P14 |
LC1D09●● LC1D09●● |
5.5 | 11.5 | 130 | 9…14 | GV2ME16 or GV2P16 |
LC1D25●● LC1D25●● |
7.5 | 15.5 | 15 50 |
13…18 | GV2ME20 or GV2P20 |
LC1D25●● LC1D25●● |
9 | 18.1 | 15 50 |
17…23 | GV2ME21 or GV2P21 |
LC1D25●● LC1D25●● |
11 | 22 | 15 50 |
20…25 | GV2ME22 or GV2P22 |
LC1D25●● LC1D25●● |
15 | 29 | 10 50 |
24…32 | GV2ME32 or GV2P32 |
LC1D32●● LC1D32●● |
18.5 22 30 |
35 41 55 |
50 50 50 |
30…40 37…50 48…65 |
GV3P40 GV3P50 GV3P65 |
LC1D50A●● LC1D50A●● LC1D65A●● |
37 | 66 | 50 100 |
62…73 40…80 |
GV3P73 GV4P80 |
LC1D80A●● LC1D80●● |
45 | 80 | 100 | 65…115 | GV4P11 | LC1D115●● |
55 | 97 | 100 | |||
75 90 110 |
132 160 195 |
70 70 35 |
10…150 100…220 100…220 |
GV5P150H GV5P220H GV5P220H |
LC1D150●● LC1F185●● LC1F225●● |