Contactor for switching 3-phase capacitor banks

Enquiry Us

Description

AC-6b contactors for capbank application
AC-6b rating 12.5kVar ~ 60kVar contactors LC1D lK are designed for switching 3-phase, single or multiple-
step capacitor banks; they conform to standards IEC 70 and 831, NFC 54-100, VDE 0560, UL and CSA.
Operating conditions
There is no need to use choke inductors for either single or multiple-step capacitor banks.
Short-circuit protection must be provided by gG type fuses rated at 1.7…2 In.
Prospective peak
current at switch-on
Reference 200 In
Maximum operating
rate
LC1-DFK, DGK, DLK, DMK, DPK
LC1-DTK, DWK
240 operating cycles/hour.
100 operating cycles/hour.
Electrical durability
at rated load
All contactor rating 400 V
690V
300 000 operating cycles.
200 000 operating cycles.

Direct connection without choke inductor

Operational power at 50/60 Hz
(θ less than 55 °C) (2)
400 V
440 V
Instantan.
auxiliary
contacts
Tightening
torque on
cable end
Basic reference.
Complete with code
indicating control
circuit voltage (1)
kVAR N/O N/C N.m
12.5
16.7
21
27
32
43
67
1
1
1
1
1
1
1
2
2
2
2
2
2
2
1.2
1.7
1.9
2.5
5
5
9
LC1DFK●●
LC1DGK●●
LC1DLK●●
LC1DMK●●
LC1DPK●●
LC1DTK●●
LC1DWK12●●
Using standard (AC1) contactor LC1D and LC1F
The selections below are made based on safety factor of 1.3 and 1.1 for harmonic effects and
capacitor tolerence. It is strongly recommended to insert choke inductors when switching on
multi-stepped capacitor banks
Operational power at 50/60 Hz
(θ less than 55 °C) (2)
Instantan.
auxiliary
contacts
Basic reference.
Complete with code
indicating control
circuit voltage (1)
AC1
Amps
400 V
440 V
kVAR
max peak
current
Amps
N/O N/C
25 5
11
560
560
1
1
1
1
LC1D09●●
LC1D12●●
32
40
50
60
15
20
25
30
850
1600
1900
2160
1
1
1
1
1
1
1
1
LC1D18●●
LC1D25●●
LC1D32●●
LC1D40A●●
80 35
40
2160
2160
1
1
1
1
LC1D50A●●
LC1D50A●●
125 45
50
60
3040
3040
3040
1
1
1
1
1
1
LC1D80●●
LC1D80●●
LC1D80●●
200 75
85
3100
3300
1
1
1
1
LC1D1156●●
LC1D1506●●
275
315
350
100
110
125
3500
4000
5000
2
2
2
2
2
2
LC1G185●●
LC1G225●●
LC1G265●●
Switching of multiple-step capacitor banks (with equal or different power ratings).
The correct contactor for each step is selected from the above table, according to the power rating
of the step to be switched.
Example: 50 kVAR 3-step capacitor bank. Temperature: 50 oC and U = 400 V or 440 V.
One 25 kVAR step: contactor LC1-DMK, one 15 kVAR step: contactor LC1-DGK and
one 10 kVAR step: contactor LC1-DFK.
(1) Standard control circuit voltages
Volts 220 230
50/60Hz M7 P7

Other voltages between 24 and 440 V, please consult our local representatives or agents.
(2) The average temperature over a 24-hour period, in accordance with IEC 70 and 831 is 45ºC.