3RV6/5 For motor protection up to 100A

For motor protection up to 100A
Class 10, without auxiliary switches

Enquiry Us

Description

Size

Rated
current

Suitable
for 3 Phase
induction motors
with P
Setting
range
for thermal
overload release
Instantaneous
overcurrent
release
Short circuit
breaking
capacity at
400 V AC
Order Number
A kW A A kA
Size S00

0.16
0.2
0.25
0.32
0.04
0.06
0.06
0.09
0.11…0.16
0.14…0.20
0.18…0.25
0.22…0.32
2.1
2.6
3.3
4.2
100
100
100
100
3RV6011-0AA10
3RV6011-0BA10
3RV6011-0CA10
3RV6011-0DA10
0.4
0.5
0.63
0.8
0.09
0.12
0.18
0.18
0.28…0.40
0.35…0.50
0.45…0.63
0.55…0.80
5.2
6.5
8.2
10
100
100
100
100
3RV6011-0EA10
3RV6011-0FA10
3RV6011-0GA10
3RV6011-0HA10
1
1.25
1.6
2
0.25
0.37
0.55
0.75
0.7…1
0.9…1.25
1.1…1.6
1.4…2
13
16
21
26
100
100
100
100
3RV6011-0JA10
3RV6011-0KA10
3RV6011-1AA10
3RV6011-1BA10
2.5
3.2
4
5
0.75
1.1
1.5
1.5
1.8…2.5
2.2…3.2
2.8…4
3.5…5
33
42
52
65
100
100
100
100
3RV6011-1CA10
3RV6011-1DA10
3RV6011-1EA10
3RV6011-1FA10
6.3
8
10
12.5
16
2.2
3
4
5.5
7.5
4.5…6.3
5.5…8
7…10
9…12.5
11…16
82
104
130
163
208
100
100
100
100
55
3RV6011-1GA10
3RV6011-1HA10
3RV6011-1JA10
3RV6011-1KA10
3RV6011-4AA10
Size S0

20
22
25
7.5
11
11
14…20
17…22
20…25
260
286
325
55
55
55
3RV6021-4BA10
3RV6021-4CA10
3RV6021-4DA10
28
32
36
40
15
15
18.5
18.5
23…28
27…32
30…36
34….60
364
400
432
480
55
55
55
55
3RV6021-4NA10
3RV6021-4EA10
3RV6021-4PA10
3RV6021-4FA10
Size S2

45
50
22
22
36…..45
40…..50
585
650
50
50
3RV5031-4GA10
3RV5031-4HA10
Size S3

63 30 45…..63 819 50 3RV5041-4JA10
75
90
100
37
45
45
57…..75
70…..90
80…..100
975
1170
1235
50
50
50
3RV5041-4KA10
3RV5041-4LA10
3RV5041-4MA10