DOL motor starter with Type 1 coordination

Type 1 Coordination
According to IEC 60439-4-1, type 1 coordination requires that in the event of a short circuit,
– contactor or starter must not present any danger to personnel or installation
– must not be able to resume operation without repair or replacement of parts

Enquiry Us

Description

Standard power
rating of 3-phase
motors in
category AC3
400/415V
Circuit-breaker
Setting ‘(1)
range
of
thermal
trips
Contactor
(1)(2)(3)
P
kW
le
HP
lq
kA
A Reference Reference
0.06 0.2 50 0.16…0.25 GV2ME02 LC1K06●●●●
or LC1D09●●
0.09 0.3 50 0.25…0.40 GV2ME03 LC1K06●●●●
or LC1D09●●
0.12
0.18
0.44
0.6
50
50
0.40…0.63 GV2ME04 LC1K06●●●●
or LC1D09●●
0.25
0.37
0.85
1.1
50
50
0.63… 1 GV2ME05 LC1K06●●●●
or LC1D09●●
0.55 1.5 50 1… 1.6 GV2ME06 LC1K06●●●●
or LC1D09●●
0.75 1.9 50 1.6… 2.5 GV2ME07 LC1K06●●●●
or LC1D09●●
1.1
1.5
2.7
3.6
50
50
2.5…4 GV2ME08 LC1K06●●●●
or LC1D09●●
2.2 4.9 50 4… 6.3 GV2ME10 LC1K06●●●●
or LC1D09●●
3 6.5 50 6… 10 GV2ME14 LC1K09●●●●
or LC1D09●●
5.5 11.5 15 9… 14 GV2ME16 LC1K12●●●●
or LC1D12●●
7.5
9
11
15
18.5
22
30
15.5
18.1
22
29
35
41
55
15
15
15
10
50
50
50
13…18
17…23
20…25
24…32
30…40
37…50
48…65
GV2ME20
GV2ME21
GV2ME22
GV2ME32
GV3P40
GV3P50
GV3P65
LC1D18●●
LC1D25●●
LC1D25●●
LC1D32●●
LC1D40A●●
LC1D50A●●
LC1D65A●●
37 66 50
100
62…73
40…80
GV3P73
GV4P80
LC1D80A●●
LC1D80●●
45
55
75
90
110
80
97
132
160
195
100
100
36
36
36
65…115
65…115
70…150
100…220
100…220
GV4P115
GV4P115
GV5P150F
GV5P220F
GV5P220F
LC1D95●●
LC1D115●●
LC1D150●●
LC1G185●●
LC1G225●●