DOL motor starter with Type 2 coordination

Type 2 Coordination
According to IEC 60439-4-1, type 2 coordination requires that in the event of a short circuit,
– contactor or starter must not present any danger to personnel or installation
– must subsequently be able to resume operation

Enquiry Us

Description

Standard power
rating of 3-phase
motors in
category AC3
400/415V
Circuit-breaker
Setting ‘(1)
range
of
thermal
trips
Contactor
(1)(2)(3)
P
kW
le
A
lq
kA
A Reference Reference
0.06 0.2 130 0.16…0.25 GV2ME02
or GV2P02
LC1D09●●
LC1D09●●
0.09 0.3 130 0.25…0.40 GV2ME03
or GV2P03
LC1D09●●
LC1D09●●
0.12
0.18
0.44
0.6
130
130
0.40…0.63 GV2ME04
or GV2P04
LC1D09●●
LC1D09●●
0.25
0.37
0.85
1.1
130
130
0.63… 1 GV2ME05
or GV2P05
LC1D09●●
LC1D09●●
0.55 1.5 130 1… 1.6 GV2ME06
or GV2P06
LC1D09●●
LC1D09●●
0.75 1.9 130 1.6… 2.5 GV2ME07
or GV2P07
LC1D09●●
LC1D09●●
1.1
1.5
2.7
3.6
130
130
2.5…4  GV2ME08
or GV2P08
LC1D09●●
LC1D09●●
2.2 4.9 130 4… 6.3 GV2ME10
or GV2P10
LC1D09●●
LC1D09●●
3 6.5 130 6… 10 GV2ME14
or GV2P14
LC1D09●●
LC1D09●●
5.5 11.5 130 9…14 GV2ME16
or GV2P16
LC1D25●●
LC1D25●●
7.5 15.5 15
50
13…18  GV2ME20
or GV2P20
LC1D25●●
LC1D25●●
9 18.1 15
50
17…23 GV2ME21
or GV2P21
LC1D25●●
LC1D25●●
11 22 15
50
20…25 GV2ME22
or GV2P22
LC1D25●●
LC1D25●●
15 29 10
50
24…32 GV2ME32
or GV2P32
LC1D32●●
LC1D32●●
18.5
22
30
35
41
55
50
50
50
30…40
37…50
48…65
GV3P40
GV3P50
GV3P65
LC1D50A●●
LC1D50A●●
LC1D65A●●
37 66 50
100
62…73
40…80
GV3P73
GV4P80
LC1D80A●●
LC1D80●●
45 80 100 65…115  GV4P11 LC1D115●●
55 97 100
75
90
110
132
160
195
70
70
35
10…150
100…220
100…220
GV5P150H
GV5P220H
GV5P220H
LC1D150●●
LC1F185●●
LC1F225●●