Description
Description | For use on |
Sold in lots of |
Reference | |
Accessories (to be ordered separately) | ||||
Pre-wiring kit allowing direct connection of the N/C contact of relay LRD01…35 or LR3D01…D35 to the contactor |
LC1D09…D18 LC1D25…D38 |
10 10 |
LAD7C1 LAD7C2 |
|
Terminal blocks (2) for clip-on mounting on 35 mm |
LRD01…35 and LR3D01…D35 LRD1508…32 LRD33••, LR3D33••, LR2D35•• |
1 1 1 |
LAD7B106 LAD7B105 LA7D3064 |
|
Everlink Terminal block for independent mounting |
LRD3••, LRD3••L, LR3D3•• |
1 | LAD96560 | |
Terminal block adaptor for mounting a relay beneath an LC1D115 or D150 contactor |
LRD3•••, LR3D3•••, LRD35•• |
1 | LA7D3058 | |
Mounting Plates (4) for screw fixing in 110mm centers |
LRD3•••, LR3D3••• LR2D35•• |
1 | LA7D902 | |
Remote stop or electrical reset device (5) |
LRD01…35 and LR3D01…D35 |
1 | LAD703• | |
Remote tripping or electrical reset device (5) |
All relays except LRD01…35 and LR3D01…D35 |
1 | LA7D03• | |
Block of insulated terminals | LR9D | 1 | LA9F103 |
(1) These pre-wiring kits cannot be used with reversing contactors.
(2) Terminal blocks are supplied with terminals protected against direct finger contact and screws
in the open, “ready-to-tighten” position.
(3) To order a terminal bloack for connection by lugs, the reference becomes LA7D30646.
(4) Do not forget to order the terminal block corresponding to the type of relay.
(5) The time for which the coil of remote tripping or electrical resetting device LA7D03 or LAD703 can
remain energised depends on its rest time: 1 s pulse duration with 9 s rest time; 5 s pulse duration
with 30s rest time; 10s pulse duration with 90 s rest time; maximum pulse duration of 20 s with a
rest time of 300 s.
Minimum pulse time: 200 ms.
(6) Reference to be completed by adding the code indicating control circuit voltage.
Volts | 24 | 110 | 220/230 |
50/60 Hz | B | F | M |
Consumption, inrush and sealed :< 100 VA | |||
d.c. | B | F | M |
Consumption, inrush and sealed:< 100 W |