Description
3-pole contactors | |||||
Standard power rating of 3-phase motors 50/60Hz in category AC-3 |
Rated operational current at 440V up to |
Instantaneous auxiliary contacts |
Basic reference, to be completed by adding the control voltage code (1) |
||
400V | AC-3 | AC-1 | Fixing (2) | ||
kw | A | A | N/O | N/C | |
Connection by screw clamp terminals | |||||
22.2 | 6 | 20 | 1 0 |
0 1 |
LC1E0610•• LC1E0601•• |
4 | 9 | 25 | 1 0 |
0 1 |
LC1E0910•• LC1E0901•• |
5.5 | 12 | 25 | 1 0 |
0 1 |
LC1E1210•• LC1E1201•• |
7.5 | 18 | 32 | 1 0 |
0 1 |
LC1E1810•• LC1E1801•• |
11 | 25 | 36 | 1 0 |
0 1 |
LC1E2510•• LC1E2501•• |
15 | 32 | 50 | 1 0 |
0 1 |
LC1E3210•• LC1E3201•• |
18.5 | 38 | 50 | 1 0 |
0 1 |
LC1E3810•• LC1E3801•• |
18.5 22 30 37 45 55 75 |
40 50 65 80 95 120 160 |
60 70 80 110 120 150 200 |
1 1 1 1 1 1 1 |
1 1 1 1 1 1 1 |
LC1E40•• LC1E50•• LC1E65•• LC1E80•• LC1E95•• LC1E120•• LC1E160•• |
Connection by bars | |||||
90 132 160 200 250 335 |
200 250 300 400 500 630 |
250 300 320 500 700 1000 |
0 0 0 0 0 0 |
0 0 0 0 0 0 |
LC1E200•• LC1E250•• LC1E300•• LC1E400•• LC1E500•• LC1E630•• |
Auxiliary contact blocks, add-on modules and accessories. | ||||||||
(1) Standard control circuit voltages. For other voltages please refer to catalogue. | ||||||||
a.c. supply | ||||||||
Volts | 24 | 48 | 110 | 220 | 240 | 380 | 415 | 440 |
LC1E06…300 | ||||||||
50Hz 60Hz |
B5 B6 |
E5 – |
F5 F6 |
M5 M6 |
U5 – |
Q5 Q6 |
N5 – |
R5 R6 |
LC1E400…630 | ||||||||
50/60 Hz | – | E7 | F7 | M7 | U7 | Q7 | N7 | R7 |
2) LC1E06 to E65: clip-on mounting on 35 mm 5 rail AM1 DP or screw fixing. LC1E80 to E95: clip-on mounting on 35 mm rail AM1DP or 75 mm rail AM1 DL or screw fixing. LC1E120 and E160: clip-on mounting on 2 x 35 mm 5 rail AM1 DP or screw fixing. |